11:55:27.829 Running procedure: 8.4.2.2.3
11:55:27.832 This procedure is enabled because the following options:
11:55:27.832 - supports.analogOutput.status == true
11:55:27.832 - supports.disable.analogOutput == true
11:55:27.833 step: 1
11:55:27.833 - Device supports disabling analog outputs
11:55:27.833 step: 2
11:55:27.833 - Configure the DUT such that all Analog Output points are uninstalled or disabled
11:55:27.839 step: 3
11:55:27.839 - Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:55:27.839 - g41v2, 2-Byte Count and Index, count: 1
11:55:27.839 - [0] - value: 10 status: 0
11:55:27.840 --A-> Direct Operate(0x05) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:55:27.840 g41v2, 2-Byte Count and Index, count: 1
11:55:27.840 [0] - value: 10 status: 0
11:55:27.841 --T-> fir: 1 fin: 1 seq: 0
11:55:27.841 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 18 dest: 1024 src: 1
11:55:27.841 --P-> 05 64 12 C4 00 04 01 00 30 DD
11:55:27.841 C0 C0 05 29 02 28 01 00 00 00 0A 00 00 64 B4
11:55:27.842 step: 4
11:55:27.842 - Read a single fragment response w/ sequence(0x00)
11:55:27.842 - Verify that the IIN field contains one of IIN(ParamError, ObjectUnknown)
11:55:27.843 <-P-- 05 64 14 44 01 00 00 04 A3 01
11:55:27.843 C0 C0 81 90 04 29 02 28 01 00 00 00 0A 00 04 81 EF
11:55:27.843 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 20 dest: 1 src: 1024
11:55:27.844 <-T-- fir: 1 fin: 1 seq: 0
11:55:27.844 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, ParamError)
11:55:27.844 g41v2, 2-Byte Count and Index, count: 1
11:55:27.844 [0] - value: 10 status: 4
11:55:27.845 step: 5
11:55:27.845 - Check that no analog control point operated
11:55:28.850 Passed procedure: 8.4.2.2.3