12:02:14.719 Running procedure: 8.21.2.2
12:02:14.724 This procedure is enabled because the following options:
12:02:14.724 - supports.disable.doubleBit == true
12:02:14.725 step: 1
12:02:14.725 - If the device is not configurable in a manner such that Double-bit Input points can be uninstalled or disabled, no further testing in this section is necessary
12:02:14.726 step: 2
12:02:14.726 - Configure the DUT such that all Double-bit Binary Input points are uninstalled or disabled
12:02:14.726 - Cycle power to the DUT
12:02:14.735 step: 3
12:02:14.735 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
12:02:14.735 - g3v0, All Objects
12:02:14.736 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
12:02:14.736 g3v0, All Objects
12:02:14.736 --T-> fir: 1 fin: 1 seq: 0
12:02:14.736 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
12:02:14.737 --P-> 05 64 0B C4 00 04 01 00 CA 8A
12:02:14.737 C0 C0 01 03 00 06 2B 4C
12:02:14.738 step: 4
12:02:14.738 - Read a single fragment response w/ sequence(0x00)
12:02:14.738 - Verify that the response is empty
12:02:14.738 <-P-- 05 64 0A 44 01 00 00 04 67 88
12:02:14.738 C0 C0 81 90 00 9B 2C
12:02:14.739 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024
12:02:14.739 <-T-- fir: 1 fin: 1 seq: 0
12:02:14.739 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
12:02:14.739 Passed procedure: 8.21.2.2