11:54:42.094 Running procedure: 8.2.1.2.7
11:54:42.108 This procedure is enabled because the following options:
11:54:42.108 - supports.binaryOutput.commands == true
11:54:42.109 step: 1
11:54:42.109 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:42.109 - g12v1, 1-Byte Count and Index, count: 1
11:54:42.109 - [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:42.111 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:42.111 g12v1, 1-Byte Count and Index, count: 1
11:54:42.111 [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:42.111 --T-> fir: 1 fin: 1 seq: 0
11:54:42.111 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:42.113 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:42.113 C0 C0 03 0C 01 17 01 00 03 01 64 00 00 00 C8 00 FD 11
11:54:42.113 00 00 00 FF FF
11:54:42.113 step: 2
11:54:42.113 - Read a single fragment response w/ sequence(0x00)
11:54:42.113 - Verify the response contains the exact object header:
11:54:42.113 - g12v1, 1-Byte Count and Index, count: 1
11:54:42.113 - [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:42.114 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:42.114 C0 C0 81 90 00 0C 01 17 01 00 03 01 64 00 00 00 9C 9A
11:54:42.114 C8 00 00 00 00 78 FB
11:54:42.114 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:42.115 <-T-- fir: 1 fin: 1 seq: 0
11:54:42.116 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
11:54:42.116 g12v1, 1-Byte Count and Index, count: 1
11:54:42.116 [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:42.117 step: 3
11:54:42.117 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:42.117 - g12v1, 1-Byte Count and Index, count: 1
11:54:42.117 - [0] - code: 3 count: 1 onTime: 100 offTime: 201 status: 0
11:54:42.118 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:42.118 g12v1, 1-Byte Count and Index, count: 1
11:54:42.118 [0] - code: 3 count: 1 onTime: 100 offTime: 201 status: 0
11:54:42.118 --T-> fir: 1 fin: 1 seq: 0
11:54:42.118 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:42.119 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:42.119 C0 C1 04 0C 01 17 01 00 03 01 64 00 00 00 C9 00 7B 6C
11:54:42.119 00 00 00 FF FF
11:54:42.121 step: 4
11:54:42.121 - Read a single fragment response w/ sequence(0x01)
11:54:42.121 - Verify the response contains the exact object header:
11:54:42.121 - g12v1, 1-Byte Count and Index, count: 1
11:54:42.121 - [0] - code: 3 count: 1 onTime: 100 offTime: 201 status: 2
11:54:42.122 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:42.122 C1 C1 81 90 00 0C 01 17 01 00 03 01 64 00 00 00 08 B9
11:54:42.122 C9 00 00 00 02 C2 B4
11:54:42.122 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:42.123 <-T-- fir: 1 fin: 1 seq: 1
11:54:42.124 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
11:54:42.124 g12v1, 1-Byte Count and Index, count: 1
11:54:42.124 [0] - code: 3 count: 1 onTime: 100 offTime: 201 status: 2
11:54:42.124 step: 5
11:54:42.124 - Check that no binary control point operated
11:54:43.129 Passed procedure: 8.2.1.2.7