11:54:40.533 Running procedure: 8.2.1.2.6
11:54:40.538 This procedure is enabled because the following options:
11:54:40.538 - supports.binaryOutput.commands == true
11:54:40.540 step: 1
11:54:40.540 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:40.540 - g12v1, 1-Byte Count and Index, count: 1
11:54:40.540 - [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:40.541 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:40.541 g12v1, 1-Byte Count and Index, count: 1
11:54:40.541 [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:40.541 --T-> fir: 1 fin: 1 seq: 0
11:54:40.541 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:40.542 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:40.542 C0 C0 03 0C 01 17 01 00 03 01 64 00 00 00 C8 00 FD 11
11:54:40.542 00 00 00 FF FF
11:54:40.544 step: 2
11:54:40.544 - Read a single fragment response w/ sequence(0x00)
11:54:40.544 - Verify the response contains the exact object header:
11:54:40.544 - g12v1, 1-Byte Count and Index, count: 1
11:54:40.544 - [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:40.545 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:40.545 C0 C0 81 90 00 0C 01 17 01 00 03 01 64 00 00 00 9C 9A
11:54:40.545 C8 00 00 00 00 78 FB
11:54:40.545 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:40.545 <-T-- fir: 1 fin: 1 seq: 0
11:54:40.546 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
11:54:40.546 g12v1, 1-Byte Count and Index, count: 1
11:54:40.546 [0] - code: 3 count: 1 onTime: 100 offTime: 200 status: 0
11:54:40.548 step: 3
11:54:40.548 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:40.548 - g12v1, 1-Byte Count and Index, count: 1
11:54:40.548 - [0] - code: 3 count: 1 onTime: 101 offTime: 200 status: 0
11:54:40.548 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:40.548 g12v1, 1-Byte Count and Index, count: 1
11:54:40.548 [0] - code: 3 count: 1 onTime: 101 offTime: 200 status: 0
11:54:40.549 --T-> fir: 1 fin: 1 seq: 0
11:54:40.549 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:40.550 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:40.550 C0 C1 04 0C 01 17 01 00 03 01 65 00 00 00 C8 00 D2 72
11:54:40.550 00 00 00 FF FF
11:54:40.551 step: 4
11:54:40.551 - Read a single fragment response w/ sequence(0x01)
11:54:40.551 - Verify the response contains the exact object header:
11:54:40.551 - g12v1, 1-Byte Count and Index, count: 1
11:54:40.551 - [0] - code: 3 count: 1 onTime: 101 offTime: 200 status: 2
11:54:40.552 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:40.552 C1 C1 81 90 00 0C 01 17 01 00 03 01 65 00 00 00 E0 7B
11:54:40.552 C8 00 00 00 02 C4 97
11:54:40.553 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:40.553 <-T-- fir: 1 fin: 1 seq: 1
11:54:40.554 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
11:54:40.554 g12v1, 1-Byte Count and Index, count: 1
11:54:40.554 [0] - code: 3 count: 1 onTime: 101 offTime: 200 status: 2
11:54:40.554 step: 5
11:54:40.554 - Check that no binary control point operated
11:54:41.559 Passed procedure: 8.2.1.2.6