11:54:32.450 Running procedure: 8.2.1.2.2
11:54:32.456 This procedure is enabled because the following options:
11:54:32.456 - supports.binaryOutput.status == true
11:54:32.458 step: 1
11:54:32.458 - Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:32.458 - g12v1, 1-Byte Count and Index, count: 1
11:54:32.458 - [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.459 --A-> Select(0x03) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
11:54:32.459 g12v1, 1-Byte Count and Index, count: 1
11:54:32.459 [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.460 --T-> fir: 1 fin: 1 seq: 0
11:54:32.460 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:32.461 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:32.461 C0 C0 03 0C 01 17 01 01 81 05 2C 01 00 00 90 01 36 C6
11:54:32.461 00 00 00 FF FF
11:54:32.463 step: 3
11:54:32.463 - Read a single fragment response w/ sequence(0x00)
11:54:32.463 - Verify the response contains the exact object header:
11:54:32.463 - g12v1, 1-Byte Count and Index, count: 1
11:54:32.463 - [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.464 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:32.464 C0 C0 81 90 00 0C 01 17 01 01 81 05 2C 01 00 00 2B 94
11:54:32.464 90 01 00 00 00 F1 F6
11:54:32.464 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:32.464 <-T-- fir: 1 fin: 1 seq: 0
11:54:32.467 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime)
11:54:32.467 g12v1, 1-Byte Count and Index, count: 1
11:54:32.467 [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.468 step: 4
11:54:32.468 - Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:32.468 - g12v1, 1-Byte Count and Index, count: 1
11:54:32.468 - [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.469 --A-> Operate(0x04) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
11:54:32.469 g12v1, 1-Byte Count and Index, count: 1
11:54:32.469 [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.469 --T-> fir: 1 fin: 1 seq: 0
11:54:32.469 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 24 dest: 1024 src: 1
11:54:32.470 --P-> 05 64 18 C4 00 04 01 00 5B 61
11:54:32.470 C0 C1 04 0C 01 17 01 01 81 05 2C 01 00 00 90 01 FE 10
11:54:32.470 00 00 00 FF FF
11:54:32.472 step: 5
11:54:32.472 - Read a single fragment response w/ sequence(0x01)
11:54:32.472 - Verify the response contains the exact object header:
11:54:32.472 - g12v1, 1-Byte Count and Index, count: 1
11:54:32.472 - [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.473 <-P-- 05 64 1A 44 01 00 00 04 A6 F0
11:54:32.473 C1 C1 81 90 00 0C 01 17 01 01 81 05 2C 01 00 00 BF B7
11:54:32.473 90 01 00 00 00 F1 F6
11:54:32.473 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 26 dest: 1 src: 1024
11:54:32.473 <-T-- fir: 1 fin: 1 seq: 1
11:54:32.474 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime)
11:54:32.474 g12v1, 1-Byte Count and Index, count: 1
11:54:32.474 [1] - code: 129 count: 5 onTime: 300 offTime: 400 status: 0
11:54:32.475 step: 6
11:54:32.475 - Check that binary control point 1 operate
11:54:32.475 Passed procedure: 8.2.1.2.2