12:02:09.734
|
|
Running procedure: 8.18.2.2
|
12:02:09.740
|
|
This procedure is enabled because the following options:
|
12:02:09.740
|
|
- supports.analog == true
|
12:02:09.741
|
|
step: 1
|
12:02:09.741
|
|
- Input analog data
|
12:02:09.742
|
|
Updated AI 1024: value=100.0, flags=1, timestamp=DNPTime(1586534529741)
|
12:02:09.742
|
|
Updated AI 1024: value=200.0, flags=1, timestamp=DNPTime(1586534529742)
|
12:02:09.742
|
|
Updated AI 41: value=100.0, flags=1, timestamp=DNPTime(1586534529742)
|
12:02:09.743
|
|
step: 2
|
12:02:09.743
|
|
- Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
|
12:02:09.743
|
|
- g30v0, All Objects
|
12:02:09.745
|
--A->
|
Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00
|
12:02:09.745
|
|
g30v0, All Objects
|
12:02:09.745
|
--T->
|
fir: 1 fin: 1 seq: 0
|
12:02:09.745
|
--L->
|
master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
|
12:02:09.746
|
--P->
|
05 64 0B C4 00 04 01 00 CA 8A
|
12:02:09.746
|
|
C0 C0 01 1E 00 06 4A 28
|
12:02:09.748
|
|
steps: 3 to 4
|
12:02:09.748
|
|
- Read a single fragment response w/ sequence(0x00)
|
12:02:09.748
|
|
- Verify that the device responds with Object 30 Variation 1-4, Qualifier 0x00, or 0x01
|
12:02:09.748
|
|
- Verify that the device correctly reports that value for various analog inputs
|
12:02:09.749
|
<-P--
|
05 64 32 44 01 00 00 04 F8 9B
|
12:02:09.749
|
|
C0 C0 81 98 00 1E 02 01 00 00 00 00 01 00 00 1E AE C8
|
12:02:09.749
|
|
02 01 29 00 29 00 01 64 00 1E 02 01 00 04 00 04 69 27
|
12:02:09.749
|
|
01 C8 00 1E 02 01 FF FF FF FF 01 00 00 13 55
|
12:02:09.749
|
<-L--
|
master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 50 dest: 1 src: 1024
|
12:02:09.749
|
<-T--
|
fir: 1 fin: 1 seq: 0
|
12:02:09.752
|
<-A--
|
Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x00 IIN(DeviceRestart, NeedTime, Class3Events)
|
12:02:09.752
|
|
g30v2, 2-Byte Start/Stop, start: 0 stop: 0
|
12:02:09.752
|
|
[0] - flags: 0x01 value: 0
|
12:02:09.752
|
|
g30v2, 2-Byte Start/Stop, start: 41 stop: 41
|
12:02:09.752
|
|
[41] - flags: 0x01 value: 100
|
12:02:09.752
|
|
g30v2, 2-Byte Start/Stop, start: 1024 stop: 1024
|
12:02:09.752
|
|
[1024] - flags: 0x01 value: 200
|
12:02:09.752
|
|
g30v2, 2-Byte Start/Stop, start: 65535 stop: 65535
|
12:02:09.752
|
|
[65535] - flags: 0x01 value: 0
|
12:02:09.753
|
|
Passed procedure: 8.18.2.2
|