| 12:00:20.586 | Running procedure: 8.13.2.3 | |
| 12:00:20.590 | This procedure is enabled because the following options: | |
| 12:00:20.590 | - supports.disable.binaryInput == true | |
| 12:00:20.591 | step: 1 | |
| 12:00:20.591 | - Device is configurable in a manner such that Binary Input points can be uninstalled or disabled. | |
| 12:00:20.592 | step: 2 | |
| 12:00:20.592 | - Configure the DUT such that all Binary Input points are uninstalled or disabled | |
| 12:00:20.592 | - Cycle power to the DUT | |
| 12:00:20.600 | step: 3 | |
| 12:00:20.600 | - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 | |
| 12:00:20.600 | - g1v0, All Objects | |
| 12:00:20.602 | --A-> | Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 |
| 12:00:20.602 | g1v0, All Objects | |
| 12:00:20.602 | --T-> | fir: 1 fin: 1 seq: 0 |
| 12:00:20.602 | --L-> | master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1 |
| 12:00:20.603 | --P-> | 05 64 0B C4 00 04 01 00 CA 8A |
| 12:00:20.603 | C0 C1 01 01 00 06 5D 5C | |
| 12:00:20.604 | step: 4 | |
| 12:00:20.604 | - Read a single fragment response w/ sequence(0x01) | |
| 12:00:20.604 | - Verify that the response is empty | |
| 12:00:20.605 | <-P-- | 05 64 0A 44 01 00 00 04 67 88 |
| 12:00:20.605 | C0 C1 81 90 00 73 EE | |
| 12:00:20.605 | <-L-- | master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 10 dest: 1 src: 1024 |
| 12:00:20.606 | <-T-- | fir: 1 fin: 1 seq: 0 |
| 12:00:20.606 | <-A-- | Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime) |
| 12:00:20.606 | Passed procedure: 8.13.2.3 |