12:00:20.037 Running procedure: 8.13.2.2
12:00:20.042 This procedure is enabled because the following options:
12:00:20.042 - supports.binaryInput == true
12:00:20.043 step: 1
12:00:20.043 - Generate a known Binary Input pattern
12:00:20.043 Updated BI 0: value=true, flags=81, timestamp=DNPTime(1586534420043)
12:00:20.043 Updated BI 41: value=true, flags=81, timestamp=DNPTime(1586534420043)
12:00:20.044 Updated BI 41: value=false, flags=1, timestamp=DNPTime(1586534420043)
12:00:20.045 step: 2
12:00:20.045 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
12:00:20.045 - g1v0, All Objects
12:00:20.046 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01
12:00:20.046 g1v0, All Objects
12:00:20.046 --T-> fir: 1 fin: 1 seq: 0
12:00:20.046 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
12:00:20.047 --P-> 05 64 0B C4 00 04 01 00 CA 8A
12:00:20.047 C0 C1 01 01 00 06 5D 5C
12:00:20.048 steps: 3 to 5
12:00:20.048 - Read any number of valid responses beginning w/ sequence(0x01) and incrementing by 1 modulo 16
12:00:20.048 - Verify that the device responds with only variations: Set(g1v1, g1v2)
12:00:20.048 - Verify that the data is reported using either 8 bit start/stop indexing (qualifier 0x00) or 16 bit start/stop indexing (qualifier 0x01)
12:00:20.048 - Verify that the response contains the expected values for the binary inputs
12:00:20.050 <-P-- 05 64 2A 44 01 00 00 04 E5 79
12:00:20.050 C0 C1 81 92 00 01 02 01 00 00 00 00 81 01 02 01 50 4B
12:00:20.050 29 00 29 00 01 01 02 01 00 04 00 04 01 01 02 01 2A 19
12:00:20.050 FF FF FF FF 01 BE 01
12:00:20.050 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 42 dest: 1 src: 1024
12:00:20.050 <-T-- fir: 1 fin: 1 seq: 0
12:00:20.053 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x01 IIN(DeviceRestart, NeedTime, Class1Events)
12:00:20.053 g1v2, 2-Byte Start/Stop, start: 0 stop: 0
12:00:20.053 [0] - flags: 0x81
12:00:20.053 g1v2, 2-Byte Start/Stop, start: 41 stop: 41
12:00:20.053 [41] - flags: 0x01
12:00:20.053 g1v2, 2-Byte Start/Stop, start: 1024 stop: 1024
12:00:20.053 [1024] - flags: 0x01
12:00:20.053 g1v2, 2-Byte Start/Stop, start: 65535 stop: 65535
12:00:20.053 [65535] - flags: 0x01
12:00:20.055 step: 6
12:00:20.055 - Generate a known Binary Input pattern
12:00:20.055 Updated BI 65535: value=true, flags=81, timestamp=DNPTime(1586534420055)
12:00:20.056 Updated BI 1024: value=true, flags=81, timestamp=DNPTime(1586534420055)
12:00:20.056 Updated BI 1024: value=false, flags=1, timestamp=DNPTime(1586534420056)
12:00:20.057 step: 7
12:00:20.057 - Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
12:00:20.057 - g1v0, All Objects
12:00:20.058 --A-> Read(0x01) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02
12:00:20.058 g1v0, All Objects
12:00:20.058 --T-> fir: 1 fin: 1 seq: 0
12:00:20.058 --L-> master: 1 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0xC4 length: 11 dest: 1024 src: 1
12:00:20.059 --P-> 05 64 0B C4 00 04 01 00 CA 8A
12:00:20.059 C0 C2 01 01 00 06 57 39
12:00:20.062 steps: 8 to 9
12:00:20.062 - Read any number of valid responses beginning w/ sequence(0x02) and incrementing by 1 modulo 16
12:00:20.062 - Verify that the device responds with only variations: Set(g1v1, g1v2)
12:00:20.062 - Verify that the data is reported using either 8 bit start/stop indexing (qualifier 0x00) or 16 bit start/stop indexing (qualifier 0x01)
12:00:20.062 - Verify that the response contains the expected values for the binary inputs
12:00:20.062 - Verify that flag behavior complies with Section 2, Note #5.
12:00:20.063 <-P-- 05 64 2A 44 01 00 00 04 E5 79
12:00:20.063 C1 C2 81 92 00 01 02 01 00 00 00 00 81 01 02 01 F4 B4
12:00:20.063 29 00 29 00 01 01 02 01 00 04 00 04 01 01 02 01 2A 19
12:00:20.063 FF FF FF FF 81 02 A7
12:00:20.063 <-L-- master: 0 pri: 1 fcb: 0 fcv: 0 func: UNCONFIRMED_USER_DATA(0x04) 0x44 length: 42 dest: 1 src: 1024
12:00:20.064 <-T-- fir: 1 fin: 1 seq: 1
12:00:20.067 <-A-- Response(0x81) fir: 1 fin: 1 con: 0 uns: 0 seq: 0x02 IIN(DeviceRestart, NeedTime, Class1Events)
12:00:20.067 g1v2, 2-Byte Start/Stop, start: 0 stop: 0
12:00:20.067 [0] - flags: 0x81
12:00:20.067 g1v2, 2-Byte Start/Stop, start: 41 stop: 41
12:00:20.067 [41] - flags: 0x01
12:00:20.067 g1v2, 2-Byte Start/Stop, start: 1024 stop: 1024
12:00:20.067 [1024] - flags: 0x01
12:00:20.067 g1v2, 2-Byte Start/Stop, start: 65535 stop: 65535
12:00:20.067 [65535] - flags: 0x81
12:00:20.068 Passed procedure: 8.13.2.2